Specifications
`
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
[SEBU7745]
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
Safety Signs and Labels
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
Oil - Change
OPERATOR STATION
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
Symbols
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
Modes Of Operation
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
Troubleshooting
ES12F, UPS 1000S and UPS 1200S Uninterruptible Power Supplys
System Description
1.1. UPS 1200
2.2. Technical Data
3.2. Specifications
4.2. Dimensions and Weights
5.2. Environmental
6.2. Safety
7.2. Ride Through Times
8.1. UPS 1000
9.2. Technical Data
10.2. Specifications
11.2. Dimensions and Weights
12.2. Environmental
13.2. Safety
14.2. Ride Through Times
UPS 1200
Technical Data
Show/hide table
Maximum kVA     | 1200     |
Maximum ekW     | 960     |
Input voltage     | 480     |
Output voltage     | 480     |
AC input current (Nominal Amps)     | 1205     |
Maximum amps incl. recharge     | 1600     |
AC output current nominal amps     | 1445     |
System efficiency     | 97 percent     |
Specifications
Show/hide table
INPUT     | |
Voltage     | 480 VAC 3 phase, 3-wire plus ground (from grounded wye source)     |
Voltage Range     | +10 percent/-15 percent (programmable)     |
Frequency     | 60Hz     |
Power Factor     | 0.99 at rated load and nominal voltage     |
Harmonic Current Distortion     | |
Linear load     | less than 3 percent at 100 percent resistive load     |
Non-linear load     | less than 8 percent with 100 percent non-linear load     |
Surge Withstand     | Meets IEEE 587/ANSI C62.41     |
Walk-in     | 1 to 15 seconds (programmable)     |
Bypass Source     | Same as input source – Synchronized frequency, phase and voltage     |
Bypass Voltage Window     | ± 10/15 percent (programmable within range)     |
OUTPUT     | |
Voltage     | 480 VAC, 3 phase, 3-wire plus ground (4-wire optional)     |
Voltage Regulation     | |
Steady-state     | ±1 percent of nominal for ± 10 percent input and balanced or unbalanced load 0.8 lag to .9 lead pf; 7 percent at –15 percent input voltage     |
Transient     | ±5 percent of nominal for 100 percent load step; or loss/ return of input     |
Recovery Time     | 50 millisecond maximum     |
Bypass Trigger     | Programmable up to ±10 percent     |
Frequency Regulation     | |
Normal Operation     | Synchronized to input     |
Free Running     | 0.1 percent stability     |
Show/hide table
Synch Window     | Adjustable over a range of at least 0.3 Hz to 3 Hz     |
Frequency Slew Rate     | Adjustable over a range of at least 0.2 Hz/second to 5 Hz/second     |
Load Power Factor     | 0.8 lag to 0.9 lead for specified regulation and rating. 0.4 lag to 0.7 lead with reduced regulation or load.     |
Voltage Unbalance and Distortion     | |
Balanced Load     | less than 1 percent voltage unbalance and less than 1 phase displacement     |
50 percent Unbalanced Load     | less than 3 percent voltage unbalance and less than 3 percent phase displacement     |
Linear Load     | less than 3 percent THD less than 2 percent SHD     |
100 percent Non Linear Load (in accordance with EN 50091-3)     | less than 5 percent THD     |
Load Imbalance     | The UPS is capable of supporting any combination of unbalanced load that does not exceed the maximum phase currents and the total output limitations of the UPS.     |
Overload Capability (nominal line without bypass)     | |
Continuous     | 105 percent     |
1 Minute     | 125 percent     |
5 Seconds     | Up to 150 percent     |
Dimensions and Weights
Show/hide table
All Cabinets     | |
Depth     | 1016 mm (40 inch)     |
Cabinet height (without DC bus)     | 1981 mm (78 inch)     |
System height (with DC bus)     | 2319 mm (91.3 inch)     |
Individual Cabinets     | |
4-wire (option)     | |
Width     | 1981 mm (78 inch)     |
Weight     | 3448 kg (7600 lb)     |
Maintenance Bypass (option)     | |
Width     | 533 mm (21.0 inch)     |
Weight     | 1134 kg (2500 lb)     |
Bottom Entry (option)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 272 kg (600 lb)     |
Input/Output     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 1134 kg (2500 lb)     |
Static Switch     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 907 kg (2000 lb)     |
Control (1)     | |
Width     | 914 mm (36.0 inch)     |
Weight     | 907 kg (2000 lb)     |
Inverter (2)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 771 kg (1700 lb)     |
Energy Storage (3)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 3040 kg (6700 lb)     |
Show/hide table
( 1 ) | Ships attached to Inverter Cabinet. |
( 2 ) | Ships attached to Control Cabinet. |
( 3 ) | 2 per Standard System |
Environmental
Show/hide table
Acoustical noise     | less than 77dBA at 1.52 m (5 ft)     |
Temperature     |     |
Operating     | 0 °C (32 °F) to 40 °C (104 °F)     |
Storage     | −25 °C (−13 °F) to 70 °C (158 °F)     |
Humidity     | 5 percent to 95 percent (non-condensing)     |
Altitude     | Up to 914.4 m (3,000 ft) (de-rate operating temperature range for higher elevation)     |
Emissions and Immunity     | FCC Class A, Subpart J of Part 15/ EN 50091-2     |
Safety
Show/hide table
UL 1778 Listed     |
CUL CAN/CSA 22.2 No. 107.1 Listed     |
Ride Through Times
Show/hide table
Number of Energy Storage Cabinets     | 100 Percent load     | 75 Percent load     | 50 Percent load     | 25 Percent load     |
2     | 13.5     | 17     | 26     | 50     |
3     | 20     | 25     | 39     | 75     |
4     | 27     | 34     | 52     | 100     |
UPS 1000
Technical Data
Show/hide table
Maximum kVA     | 1000 rated at kW     |
Maximum ekW     | 900     |
Input voltage     | 380, 400, 415     |
Output voltage     | 380, 400, 415     |
AC input current (Nominal Amps)     | 1475, 1400, 1350     |
Maximum amps incl. recharge     | 1600     |
AC output current nominal amps     | 1445, 1445, 1393     |
System efficiency     | 94 percent     |
Specifications
Show/hide table
INPUT     | |
Voltage     | 380, 400, 415 VAC 3 phase, 3-wire plus ground (from grounded wye source)     |
Voltage Range     | +10 percent/-15 percent (programmable) + 10% at 380 V     |
Frequency     | 50Hz or 60 Hz     |
Power Factor     | 0.99 at rated load and nominal voltage     |
Harmonic Current Distortion     | |
Linear load     | less than 3 percent at 100 percent resistive load     |
Non-linear load     | less than 8 percent with 100 percent non-linear load     |
Surge Withstand     | Meets IEEE 587/ANSI C62.41     |
Walk-in     | 1 to 15 seconds (programmable)     |
Bypass Source     | Same as input source – Synchronized frequency, phase and voltage     |
Bypass Voltage Window     | ± 10/15 percent (programmable within range) +10% at 380 V     |
OUTPUT     | |
Voltage     | Same as input, galvanically isolated 3-phase, 4-wire plus ground     |
Voltage Regulation     | |
Steady-state     | ±1 percent of nominal for ± 10 percent input and balanced or unbalanced load, 7 percent at –15 percent input voltage and rated load     |
Transient     | ±5 percent of nominal for 50 percent load step or loss return of input     |
Recovery Time     | 50 millisecond maximum     |
Bypass Trigger     | Programmable up to ±10 percent     |
Frequency Regulation     | |
Normal Operation     | Synchronized to input     |
Free Running     | 0.1 percent stability     |
Show/hide table
Synch Window     | Adjustable over a range of at least 0.3 Hz to 3 Hz     |
Frequency Slew Rate     | Adjustable over a range of at least 0.3 Hz/second to 3 Hz/second     |
Load Power Factor     | 0.8 lag to 0.9 lead for specified regulation and rating. 0.4 lag to 0.7 lead with reduced regulation or load.     |
Voltage Distortion     | |
Balanced Load     | less than 1 percent voltage unbalance and less than 1 degree of phase displacement     |
50 percent Unbalanced Load     | less than 3 percent voltage unbalance and less than 3 degrees phase displacement     |
Linear Load     | less than 3 percent THD less than 2 percent SHD     |
100 percent Non Linear Load (in accordance with EN 50091-3)     | less than 5 percent THD     |
Load Imbalance     | The UPS is capable of supporting any combination of unbalanced load that does not exceed the maximum phase currents and the total output limitations of the UPS.     |
Overload Capability (nominal line without bypass)     | |
Continuous     | 105 percent     |
1 Minute     | 125 percent     |
5 Seconds     | Up to 150 percent     |
Dimensions and Weights
Show/hide table
All Cabinets     | |
Depth     | 1016 mm (40 inch)     |
Cabinet height (without DC bus)     | 1981 mm (78 inch)     |
System height (with DC bus)     | 2319 mm (91.3 inch)     |
Individual Cabinets     | |
4-wire (option)     | |
Width     | 1981 mm (78 inch)     |
Weight     | 3448 kg (7600 lb)     |
Maintenance Bypass (option)     | |
Width     | 533 mm (21.0 inch)     |
Weight     | 1134 kg (2500 lb)     |
Bottom Entry (option)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 272 kg (600 lb)     |
Input/Output     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 1134 kg (2500 lb)     |
Static Switch     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 907 kg (2000 lb)     |
Control (1)     | |
Width     | 914 mm (36.0 inch)     |
Weight     | 907 kg (2000 lb)     |
Inverter (2)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 771 kg (1700 lb)     |
Energy (3)     | |
Width     | 1067 mm (42.0 inch)     |
Weight     | 3040 kg (6700 lb)     |
Show/hide table
( 1 ) | Ships attached to Inverter Cabinet. |
( 2 ) | Ships attached to Control Cabinet. |
( 3 ) | Each CSHV, 2 per System |
Environmental
Show/hide table
Acoustical noise     | less than 77dBA at 1.52 m (5 ft)     |
Temperature     |     |
Operating     | 0 °C (32 °F) to 40 °C (104 °F)     |
Storage     | −25 °C (−13 °F) to 70 °C (158 °F)     |
Humidity     | 5 percent to 95 percent (non-condensing)     |
Altitude     | Up to 914.4 m (3,000 ft) (de-rate operating temperature range for higher elevation)     |
Emissions and Immunity     | FCC Class A, Subpart J of Part 15/ EN 50091-2     |
Safety
Show/hide table
EN 50091-1-1     |
CE Mark     |
Ride Through Times
Show/hide table
Number of Energy Storage Cabinets     | 100 Percent load     | 75 Percent load     | 50 Percent load     | 25 Percent load     |
2     | 14     | 19     | 28     | 56     |
3     | 21     | 28     | 42     | 84     |
4     | 28     | 37     | 56     | 112     |
Information System:
C13 and C15 Engines for Combat and Tactical Vehicles
PTO Shutdown Timer - Test
C13 and C15 Engines for Combat and Tactical Vehicles
Output Selections
C12 Marine Engines
Engine Oil Cooler - Remove
C15 Industrial Engine
Customer Specified Parameters Table
3126B Petroleum Engine
Turbocharger - Inspect
C7 Engines for Caterpillar Built Machines
Air Inlet and Exhaust System - Inspect
3126B Petroleum Engine
Fuel System Pressure - Test
C12 Marine Engines
Inlet and Exhaust Valves - Remove and Install
C13 and C15 Engines for Combat and Tactical Vehicles
Neutral Switch Circuit - Test
C12 Marine Engines
Inlet and Exhaust Valve Springs - Remove and Install
C12 Marine Engines
Exhaust Manifold - Remove and Install
C12 Marine Engines
Turbocharger - Install
C12 Marine Engines
Water Pump - Remove
C12 Marine Engines
Water Pump - Disassemble
C12 Marine Engines
Water Pump - Assemble
2004/10/01
A New Fuel Transfer Pump is Used {1256}
C12 Marine Engines
Water Temperature Regulator - Remove and Install
C12 Marine Engines
Water Outlet Manifold - Remove
C12 Marine Engines
Auxiliary Water Pump - Remove
G3516C and G3516E Gas Engines
Camshaft
C12 Marine Engines
Aftercooler - Remove
G3516C and G3516E Gas Engines
Camshaft
G3520C and G3520E Engines
Camshaft
G3516C and G3516E Gas Engines
Camshaft