Single Unit Operation
`
D348 MARINE ENGINE
[GEG00306]
ENGINE ARRANGEMENT
1.1. Initial Start-Up
2.1. Starting
3.1. Stopping
Initial Start-Up
- 1. Remove the left side access panel of the generator.
- 2. Loosen the locknuts on the voltage droop, voltage level, and voltage gain controls.
- 3. Turn the voltage droop control (1) counterclockwise to zero droop and tighten the locknut.
VOLTAGE ADJUSTMENT CONTROLS (SR4 Generator Shown)
1. Voltage Droop 2. Voltage Level 3. Voltage Gain 4. Circuit Breaker (SR4 Generator Only)
- 4. Turn the gain control (3) counterclockwise to zero, then turn the gain control to about 1/4 of full range of clockwise travel.
- 5. Perform required maintenance on engine before starting.
- 6. Start the engine and allow it to warm.
- 7. Increase engine speed to full governed speed (high idle).
- 8. Observe the voltmeter reading. If desired voltage is not indicated, set no load voltage with voltage level control (2).
- 9. Close the load circuit breaker and apply full load gradually. Adjust governor control until nameplate frequency is on the Hertz meter.
- 10. a. If voltmeter reading increases with full load applied, turn gain control (3) slightly in counterclockwise direction.
- b. If voltmeter reading decreases with full load applied, turn gain control (3) slightly in clockwise direction.
- 11. Remove load, adjust voltage level control (2) if necessary to obtain desired voltage.
- 12. Apply the load, observe voltmeter reading. Repeat steps 9 thru 12 until no load voltage equals full load voltage.
- 13. Tighten the locknuts on all controls and install the access panel of the generator.
- 14. Circuit breaker (4) will open if excessive field current should occur. Push to reset the circuit breaker. If breaker opens again, contact your AVSpare dealer.
Starting
- 1. Make all preliminary engine starting checks.
- 2. Be sure the main or line circuit breaker is open.
- 3. Start the engine and allow it to warm up.
- 4. Adjust to full load RPM.
- 5. Close the main circuit breaker.
- 6. Apply the load. Do not try to apply full load in one move, rather apply the load in increments to maintain system frequency at a constant level.
- 7. Readjust governor for rated frequency.
Stopping
- 1. Remove the load in increments.
- 2. Open the circuit breaker.
- 3. Allow the engine to run for 5 minutes to cool.
- 4. Stop the engine.
Information System:
D348 MARINE ENGINE
Generator Set Control Panel (If Equipped)
D348 MARINE ENGINE
Generator Performance
D348 MARINE ENGINE
Generator Lead Connections
D348 MARINE ENGINE
Operating Under Abnormal Conditions
D348 MARINE ENGINE
Shutoff Devices
D348 MARINE ENGINE
Emergency Alarms
D348 MARINE ENGINE
Automatic Start-Stop
D348 MARINE ENGINE
Woodward Governor Operation
D348 MARINE ENGINE
Operating Engine And Marine Gear
D348 MARINE ENGINE
Starting The Engine
D348 MARINE ENGINE
General
D346 MARINE ENGINE
Power Coupling System
D348 MARINE ENGINE
Parallel Operation
D348 MARINE ENGINE
Generator Lubrication and Maintenance
D348 MARINE ENGINE
Lubrication And Maintenance Chart D346-D348-D349 (40J1-Up), (38J1-Up), (62P1-Up) Marine Engines
D348 MARINE ENGINE
Engine Lubrication System
D348 MARINE ENGINE
Air Induction And Exhaust System
D348 MARINE ENGINE
Fuel System
D348 MARINE ENGINE
Cooling System
D348 MARINE ENGINE
Electrical System
D348 MARINE ENGINE
Power Coupling System
G333 & 3306 NATURAL GAS ENGINES
Gas Engine Operation
G333 & 3306 NATURAL GAS ENGINES
Starting
G333 & 3306 NATURAL GAS ENGINES
Attachments